Commissioning
5.10 Acceptance tests for the safety functions
5.10.2
Reduced acceptance test after expanding the function
A full acceptance test is necessary only after first commissioning. A reduced acceptance test
is sufficient when safety functions are expanded.
Table 5- 4
Measure
Changing a single limit (e.g. SLS
level).
Functional expansion of the
machine (additional drive).
Functional expansion of a drive
(e.g. additional SLS level or new
safety function following a
firmware update).
Transfer of inverter settings to
other identical machines by means
of series commissioning.
See also Section: Reduced acceptance test after component replacement (Page 266).
158
Reduced acceptance test after expanding the function
Acceptance test
Check the modified limit
value.
Check the safety functions
of the new drive.
Check the additional
functions.
Check the control and
feedback signal of all safety
functions.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Documentation
Supplement function table
•
Log modified settings
•
Log the new checksum
•
Countersignature
•
Supplement machine overview
•
Supplement order number and
•
firmware version of the drive
Supplement function table
•
Log the settings of the new
•
drive
Log the new checksum
•
Countersignature
•
Supplement function table
•
Log modified settings
•
Log the new checksum
•
Countersignature
•
Supplement machine
•
description
Log modified settings
•
Check the checksums
•
Check the firmware versions
•
Function Manual, 04/2014, FW V4.7, A5E34261271B AA