Siemens SINAMICS G120 Function Manual page 293

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

3.
You have performed the acceptance test of the SLS function.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
2.5.
Check that the correct motor is running.
The following tests depend on how you have set the SLS function during
commissioning:
First diagram:
The inverter responds with STOP A in
the event of a limit violation.
2.6.
The inverter signals the following:
C01714 and C30714 (safe velocity
limit exceeded)
C01700 and C30700 (STOP A
initiated)
2.7.
Analyze the trace.
After SLS is selected, the inverter signals "SLS is active" (r9722.4 = 1).
The inverter signals the selected SLS level (r9722.9 and r9722.10).
If r9714[0] exceeds the active SLS limit, the inverter signals an internal event
(r9722.7 = 0).
STOP A in the event of a limit value
violation
If r9714[0] exceeds the active SLS
limit, the motor coasts down to a
standstill (r9722.0 = 1).
Deselect SLS
3.1.
Deselect SLS.
3.2.
Check: SLS is not active (r9722.4 = 0).
3.3.
Acknowledge the messages for the safety functions.
A.1 Examples of acceptance tests
Second diagram:
The inverter responds with STOP B in
the event of a limit violation.
The inverter signals the following:
C01714 and C30714 (safe velocity
limit exceeded)
C01701 and C30701 (STOP B
initiated)
C01700 and C30700 (STOP A
initiated)
STOP B in the event of a limit value
violation
If r9714[0] exceeds the active SLS
limit, the motor brakes on the OFF3
ramp (r9722.1 = 1).
After braking, STO is active
(r9722.0 = 1).
Appendix