Sls Without Braking Ramp Monitoring - Siemens SINAMICS G120 Function Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.6.2.2

SLS without braking ramp monitoring

Selecting and deselecting SLS
If the machine control selects the SLS safety function via a safety input or via the PROFIsafe
safe communication , then the motor behaves differently depending on the absolute value of
the load speed. These two scenarios are described below.
Scenario 1: The absolute value of the load speed is less than the setpoint speed limit.
Function
1. The motor continues to follow the speed setpoint.
2. The inverter monitors the speed after the delay time has expired.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
Figure 6-23
Selecting and deselecting the SLS safety function at low speeds
Operation
6.6 Safely Limited Speed (SLS)
193