A.1 Examples of acceptance tests
Procedure
To perform the acceptance test of the SS1 function, proceed as follows:
1.
2.
3.
4.
You have completed the acceptance test of the SS1 function.
286
The inverter is ready
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
SS1 is not active (r9722.1 = 0).
Go online with the STARTER and configure the following trace:
Trigger on variable - bit pattern (r9720.1 = 0)
Record the following values: r9714[0], r9714[1], r9722
Display the bits r9722.0/.1
Select the time interval and pretrigger so you can recognize the selection
of SS1 and the transition into the subsequent STO state.
Start the trace.
Switch on motor
2.1. Enter a speed setpoint ≠ 0.
2.2. Switch on the motor (ON command).
2.3. Check that the correct motor is running.
Select SS1
3.1. Select SS1 while the motor is switched on.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2. Check: The inverter signals neither faults nor alarms of the safety
functions (r0945[0...7], r2122[0...7]).
3.3. Analyze the trace.
SS1 is active after selecting SS1 (r9722.1 = 1).
The motor brakes on the OFF3 ramp.
STO becomes active if the velocity drops below the shutdown
velocity p9560 (r9722.0 = 1).
The recorded curves of r9714[0] and r9714[1] are approximately
parallel.
Deselect SS1
4.1. Deselect SS1.
4.2. Check the following:
SS1 is not active (r9722.1 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA