Operation
6.13 List of alarms and faults
Signal
Cause
Complete information on the messages is available in the List Manual.
C01712
Defect when processing F-IO
(alarm)
1)
C01714
Safely limited speed exceeded
(alarm)
1)
C01716
Tolerance for safe direction of motion
(fault)
exceeded
C01770
Discrepancy error of the safety inputs
(fault)
or outputs.
A01772
Test stop safety inputs/outputs
active.
F01773
Test stop error
A01774
Test stop required
A01795
Wait time after exiting safe pulse
suppression expired
A01796
Waiting for communication
C01798
Test stop running
(alarm)
C01799
Acceptance test mode active
(alarm)
F30600
STOP A initiated.
More detailed information is provided
by fault value r0949
F30611
Defect in a monitoring channel.
More detailed information is provided
by fault value r0949.
A30620,
Safe torque off active
F30620
A30621,
Safe Stop 1 active
F30621
F30625
Sign-of-life error in the Safety data
248
Remedy
1. Check the F-DI wiring.
2. Check the setting of the safety functions.
3. Perform an acceptance test.
1. Check the speed setpoint received from the higher-level control.
2. Check the SLS limits.
Check the tolerance setting for the SDI function.
Check the F-DI wiring.
The alarm automatically disappears after successfully ending or
canceling (error) the forced dormant error detection (test stop).
1. Check the wiring of the safety output.
2. Start the forced dormant error detection.
The time to carry out the forced dormant error detection (test stop)
has expired (p10003).
Start the forced dormant error detection of the safety output.
The wait time of 5 seconds has expired, and the motor was not
switched on. See also the sections:
Switching on the motor when SLS is active (Page 201)
Switching on the motor when SSM is active (Page 213)
Switching on the motor when SDI is active (Page 219)
Check the operating state of the F host.
Check the communication connection to the F host.
Not necessary. The inverter withdraws the message after the forced
dormant error detection has been completed.
Not necessary. The inverter withdraws the message after the end of
the acceptance test mode.
1. Select STO.
2. Deselect STO.
3. If it cannot be acknowledged, replace the Control Unit.
Fault values and remedies are described under fault F01611.
Not necessary.
Not necessary.
1. Select STO.
2. Deselect STO.
3. If it cannot be acknowledged, replace the Control Unit.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA