Commissioning
5.6 Setting basic functions
Figure 5-6
Procedure
In order to prevent the safety-related inputs of the safety functions unintentionally controlling
"standard" functions in the inverter, proceed as follows:
1. Select the inputs/outputs in STARTER in the project navigator.
2. Select the screen for the digital inputs.
3. Remove all digital input interconnections that you use as safety-related input F-DI:
4. If you use the CDS dataset switchover, you must delete the digital input connections for
all CDS.
Figure 5-7
You have now prevented safety-related inputs in the safety functions controlling "standard"
functions in the inverter.
102
Example: Assignment of digital inputs DI 4 and DI 5 with STO
Removing the DI 4 and DI 5 digital-input connections
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA