Procedure
To perform an acceptance test of the STO function as part of the extended functions,
proceed as follows:
1.
2.
3.
4.
You have performed the acceptance test of the STO function.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
The inverter is ready
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
STO is not active (r9722.0 = 0).
Switch on motor
2.1.
Enter a speed setpoint ≠ 0.
2.2.
Switch on the motor (ON command).
2.3.
Check that the correct motor is running.
Select STO
3.1.
Select STO while the motor is running.
3.2.
Check the following:
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it
remains at a standstill.
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
The inverter signals the following: "STO is active" (r9722.0 = 1).
Deselect STO
4.1.
Deselect STO.
4.2.
Check the following:
STO is not active (r9722.0 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
A.1 Examples of acceptance tests
Appendix
Status
281