Table of Contents

Advertisement

3. Close the screen form.
4. Press the button for the "STO" function:
5. Set the following:
6. Close the screen form.
You have set the forced dormant error detection (test stop) of the extended functions.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
This signal starts the forced dormant error detection and sets the remaining
monitoring time to the value
input or a bit in the fieldbus control word.
You must conduct a forced dormant error detection (test stop) for this signal.
Interconnect this signal, for example with a digital output of your choice or a status bit
in the fieldbus.
Time until the next test stop
This input field is only visible if you have selected PROFIsafe as interface. Initially,
you can ignore the setting. See also section: Configuring PROFIsafe in the converter
(Page 127).
monitoring time = maximum value (9000 hours). This means that the forced
dormant error detection monitoring for the basic functions is deactivated.
This monitoring is not required when using the extended functions, as the forced
dormant error detection of the extended functions also includes the forced dormant
error detection of the basic functions.
No setting is required.
If necessary, interconnect the status of the STO function with a digital output of
your choice, for example.
. Interconnect this signal, for example, with a digital
Commissioning
5.7 Setting extended functions
105