Commissioning
5.7 Setting extended functions
Feedback signal SDI when the motor is switched off
You can select as to whether the SDI function should remain active when the motor is
switched off.
● With the motor switched off, the inverter freezes the "SDI active" signal.
● When the motor is switched off, STO is active.
Figure 5-25
See also Section: Switching off the motor when SDI is active (Page 217).
Parameter
p9501.00
p9501.17
p9509.08
p9564
p9565
p9566
r9722.12
r9722.13
p1135
148
Feedback signal SDI when the motor is switched off
Left: SDI becomes inactive. Right: SDI remains active
Description
1 signal: Enable extended functions.
0 signal: Disable extended functions.
1 signal: Enable SDI
0 signal: Inhibit SDI
1 signal: SDI becomes inactive when the motor is switched off
0 signal: SDI remains active when the motor is switched off
Tolerance (Factory setting: 12 degrees)
Delay time (Factory setting: 100 ms)
Stop response (Factory setting: 1)
0: STOP A
1: STOP B
1 signal: SDI positive active
1 signal: SDI negative active
OFF3 ramp-down time
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA