Settings For Acceptance Test - Siemens SINAMICS G120 Function Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

5.7.8.2

Settings for acceptance test

In order to be able to approach the monitoring limit of the safety function during the
acceptance test, you must temporarily deactivate speed limiting in the inverter.
Starter offers you the possibility to temporarily deactivating speed limiting.
Procedure
To prepare for acceptance, proceed as follows:
1. In the main screen form of the extended functions, select the "Acceptance mode" button.
2. Set the time in which the inverter deactivates its internal speed limiting. During the
3. Close the screen form.
You have made the preparations for the function to be accepted.
Parameter
p9558
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
acceptance test, you must reach the monitored limit value within this time.
After this time expires, the inverter exits the acceptance mode and reactivates its internal
speed limiting.
Acceptance test mode time limit (factory setting 40000 ms)
Maximum time limit: 100 seconds.
Commissioning
5.7 Setting extended functions
149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents