Signal
Cause
Complete information on the messages is available in the List Manual.
C01711
Defect in a monitoring channel
(alarm)
1)
Fault value r2124 provides more
detailed information.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
Remedy
The complete list of the r2124 fault values is provided in the List
Manual.
0 ... 2: Fault in data cross-check between processor 1 and
processor 2. Remedy: Please refer to the List Manual.
3: Difference of the position actual value (r9713) between the two
monitoring channels is greater than the tolerance in
p9542. See also Section: Setting the gear ratio and actual value
tolerance (Page 107).
4 ... 43: Fault in data cross-check between processor 1 and
processor 2. Remedy: Please refer to the List Manual.
44 ... 57: The tolerance value for the monitoring function differs
between the two monitoring
channels. See also Section: Setting the gear ratio and actual value
tolerance (Page 107).
58 ... 999: Fault in data cross-check between processor 1 and
processor 2. Remedy: Please refer to the List Manual.
1000: Check (watchdog) timer has expired.
Too many signal changes at the F-DI
Remedy:
Check the F-DI wiring (contact problems).
1001: Initialization error of the check timer.
Remedy: Power on reset
Upgrade inverter firmware
1005: Pulses already canceled for test stop selection.
1011: Acceptance test status between the monitoring channels differ.
Diagnostics in the List Manual under r9571.
1020: Cyclic communication failure between the monitoring
channels.
Remedy: Power on reset
Replace the Control Unit or the inverter.
1040: Pulses in active encoderless monitoring functions canceled.
Deselect the active safety function.
Select and then deselect STO.
When the SLS monitoring function is active, you must switch on
the motor within 5 s of deselecting STO.
1041: Current value too low for encoderless actual value acquisition.
Reduce the minimum current (p9588).
1042: Current or voltage plausibility error.
Increase the ramp-up and ramp-down time (p1120/p1121).
Check whether the current and speed control settings are correct
(torque-forming, field-forming current and
actual speed value must not fluctuate).
Reduce the dynamic response of the setpoint.
Increase the minimum current (p9588).
Maintain an adequate wait time before switching on the motor,
also see:
Switching on the motor when SLS is active (Page 201)
Switching on the motor when SSM is active (Page 213)
Switching on the motor when SDI is active (Page 219)
1043: Too many acceleration processes.
Increase the voltage tolerance (p9589).
Operation
6.13 List of alarms and faults
247