Combinations and Limitations
With the SCTE 104 Channels a many-to-many relation can be set up between the
GPI pins and the encoder cores of VCMs. This means:
Different GPI cards fitted in the same unit can not send messages to the same
encoder core. This is because channels belong to GPI cards and one encoder core
can use only one channel for SCTE 104 input.
5.4.4.4.6
Alarm Relay
The alarm relay function is initiated by an alarm relay and a fail relay. The alarm
relay is energized when there is no active alarm condition and de-energized when
an alarm with the severity Major is raised or cleared by the unit. The fail relay is
energized when there is no active fail condition and de-energized when an alarm
with the severity Critical is raised by the unit. A loss of power is signaled as both an
alarm and a fail condition.
The alarm relay function is not configurable. At the same time, it is possible to
configure the severities of the unit alarms. To do so, browse to the Dashboard page
and select the All tab in the Alarm Monitor widget. An expandable box is displayed
for the host, and one for each card inserted in the chassis. By expanding a box, the
individual alarms can be selected and the appropriate severity level can be set.
Figure 5.28 Alarm Severity Configuration
EN/LZT 790 0023/1 R16A
More pins of the same GPI card can be configured to send messages to the
same set of encoder cores. This is achieved with selecting the same channel for
them on the GPI Input Pin Setup panel.
More encoder cores (of the same VCM or different VCMs) can be configured to
get messages from the same set of pins of a GPI card. This is achieved with
selecting the same channel for them on the SCTE 104 Input / Encoder panel.