Lenovo System x3500 M5 Type 5464 Installation And Service Manual page 435

Hide thumbs Also See for System x3500 M5 Type 5464:
Table of Contents

Advertisement

User Response
1. Check the system-event log for DIMM failure events (uncorrectable or PFA) and correct the
failures.
2. Re-enable mirroring in the Setup utility.
• 800b0509-1301xxxx : Non-redundant:Insufficient Resources for [RedundancySetElementName]
has asserted. (Power Resource)
This message is for the use case when a Redundancy Set has transitioned to Non-redundant:Insufficient
Resources.
May also be shown as 800b05091301xxxx or 0x800b05091301xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Redundant Power Supply
SNMP Trap ID
9
CIM Information
Prefix: PLAT ID: 0810
User Response
1. Power load may be handled by remaining power supply. The system will attempt to throttle to
avoid a power supply over-current condition. But a system shutdown may happen anyway if
the power load is too great.
2. Reduce the total power consumption by removing newly added or unused options like drives or
adaptors.
3.
Use the Lenovo Power Configurator utility to determine current system
power consumption. For more information and to download the utility, go to
https://www.ibm.com/support/entry/myportal/docdisplay?lndocid=LNVO-PWRCONF.
4. Replace the power supply with higher rated power.
• 800b050a-1e81xxxx : Non-redundant:Insufficient Resources for [RedundancySetElementName]
has asserted. (Fan Zone 1)
This message is for the use case when a Redundancy Set has transitioned to Non-redundant:Insufficient
Resources.
May also be shown as 800b050a1e81xxxx or 0x800b050a1e81xxxx
Appendix A. Integrated Management Module II (IMM2) error messages
419

Advertisement