SNMP Trap ID
4
CIM Information
Prefix: PLAT ID: 0522
User Response
1. Make sure that there are no obstructions, such as bundled cables, to the airflow from the
power-supply fan.
2.
Use the Lenovo Power Configurator utility to ensure current system power
consumption is under limitation. For more information and to download the utility, go to
https://www.ibm.com/support/entry/myportal/docdisplay?lndocid=LNVO-PWRCONF.
3. Replace power supply n. (n = power supply number)
• 8007020d-2582xxxx : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (RAID Vol State)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 8007020d2582xxxx or 0x8007020d2582xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Other
SNMP Trap ID
50
CIM Information
Prefix: PLAT ID: 0522
User Response
None
• 8007020f-2201xxxx : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (TXT ACM Module)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 8007020f2201xxxx or 0x8007020f2201xxxx
Severity