5. Replace the PCIe adapters.
6. Replace the riser card.
• 806f0507-0301xxxx : [ProcessorElementName] has a Configuration Mismatch. (CPU 1)
This message is for the use case when an implementation has detected a Processor Configuration
Mismatch has occurred.
May also be shown as 806f05070301xxxx or 0x806f05070301xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - CPU
SNMP Trap ID
40
CIM Information
Prefix: PLAT ID: 0062
User Response
1. Make sure that the installed microprocessors are compatible with each other.
2. (Trained technician only) Reseat microprocessor n.
3. (Trained technician only) Replace microprocessor n. (n = microprocessor number)
• 806f0507-0302xxxx : [ProcessorElementName] has a Configuration Mismatch. (CPU 2)
This message is for the use case when an implementation has detected a Processor Configuration
Mismatch has occurred.
May also be shown as 806f05070302xxxx or 0x806f05070302xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - CPU
SNMP Trap ID
580
System x3500 M5 Installation and Service Guide