Siemens Op (Ethernet) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

15.4.4

SIEMENS OP (Ethernet)

Device name
variable memory (V)
Input relay (I)
*3
Output relay (Q)
Bit device
Bit memory (M)
The bit specification of the word device (except
variable memory, Input relay, Output relay, Bit
memory, Timer, Counter)
variable memory (VW)
Input relay (IW)
*3
Output relay (QW)
Bit memory (MW)
*1*2*4
Timer (T)
**1*2*4
Counter (C)
Word device
Data register (DB)
*1
Data format to input into Timer (T), Counter (C) varies according to a type of the PLC.
• S7-300/400: BCD code
• S7-200: BIN code
*2
S-1200 does not support Timer (T), Counter (C).
*3
Writing is possible only while the PLC is running.
*4
Only 16-bit (1-word) designation is allowed.
Setting range
V0 to V102397
I0 to I655357
Q0 to Q655357
M0 to M655357
Setting range of each word device
VW0 to VW10238
IW0 to IW65534
QW0 to QW65534
MW0 to MW65534
T0 to T65535
C0 to C65535
DB1.DBW0 to DB1.DBW65534
DB2.DBW0 to
DB2.DBW65534
:
DB4094.DBW0 to DB4094.DBW65534
DB4095.DBW0 to DB4095.DBW65534
15.4 Device Range that Can Be Set
Device No.
representation
Decimal + Octal
Decimal
Decimal
15
15 - 29