(4) RS-232 connection diagram 4)
*1
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
➠
(3) RKC temperature controller side connector
Use the connector compatible with the RKC temperature controller side module.
For details, refer to user's manual of the RKC temperature controller side.
9 - 32
9.3 Connection Diagram
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
For the terminal number of the temperature controller, refer to the following table.
Signal
FB400
name
FB900
SG
SD(TXD)
RD(RXD)
1.4.1 GOT connector specifications
RKC temperature controller side
(Modular connector) * 1
PF900
PF901
25
25
26
26
27
27
SD(TXD)
RD(RXD)
SG
Terminal No.
HA400/401
HA900/901
Communication 1
Communication 2
13
25
14
26
15
27
MA900
MA901
44
45
46