15.2 Serial Connection

15.2.1
System configuration for connecting to SIMATIC S7-300/400 series
■1. When connecting to one PLC
SIMATIC
S7-300/400
series
PLC
Series
HMI Adapter
SIMATIC
MLFB:
S7-300/400
6ES7 972-0CA11-0XA0
*1
Product manufactured by Siemens AG. For details of this product, contact Siemens AG.
*2
When a GT10-C02H-6PT9P unit of the sub version A or B is used, do not ground the case of the D-sub (9-pin) connector.
*3
GT25-W, GT2505-V does not support the option device.
HMI Adapter
Connection cable
Cable model
Communication
*1
Connection diagram
Type
GT09-C30R20801-9S
RS232 connection
diagram 1)
RS-232
RS232 connection
diagram 2)
GOT
Connection cable
Max.
Option device
distance
number
- (Built into GOT)
(3m)
or
15m
GT15-RS2-9P
GT10-C02H-
6PT9P
15m
- (Built into GOT)
15.2 Serial Connection
Communication driver
SIEMENS S7-300/400
GOT
Number of
connectable
*3
Model
equipment
1 GOT for 1 HMI
Adapter
*2
15