Mitsubishi Electric GOT2000 Series Connection Manual page 197

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. Sequence program
To communicate the MP2000 series or MP920 series with the GOT2000 series, the ladder program to receive
messages is required. When connecting the MP2000 series or MP920 series with multiple GOTs, ladder programs to
receive messages for each GOT are required.
ladder program to receive messages
0000
IF
0000
SB000001 == true
NL-1
0001
FOR
0001
Variable I
NL-2
Init
00000
Max
00031
Step
00001
0002
STORE
0002
Source 00000
NL-3
Dest DW00000i
END_FOR
0003
0003
NL-2
STORE
0004
0004
Source 00001
NL-2
Dest DW00002
0005
STORE
0005
Source 00000
NL-2
Dest DW00008
0006
STORE
0006
Source 00000
NL-2
Dest DW00009
0007
STORE
0007
Source 00000
NL-2
Dest DW00010
0008
STORE
0008
Source 00000
NL-2
Dest DW00011
STORE
0009
0009
Source 00000
NL-2
Dest DW00012
Sets parameters in the first scan after startup.
(Low-speed scan (DWGL): SB000003,
High-speed scan (DWGH): SB000001)
Clears DW register to zero
*1
Sets the connection number
*2
Sets the coil offset
*2
Sets the input relay offset
*2
Sets the input register offset
*2
Sets the holding register offset
*3
Write range: LO
6.3 Ethernet Connection
6
6 - 31

Advertisement

Table of Contents
loading