Station Number Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■5. Connecting to NP1L-RS1, NP1L-RS2,
NP1L-RS3, NP1L-RS4, NP1L-RS5
(1) Communication settings
Make the communication settings using setting switches.
Switch
MODE switch
RS485 station No. switch
RS485 terminator switch
*1
Set the MODE switch so that the communication port of the general communication module to be connected to the GOT operates
as a loader.
*2
The switch is not used for connection with the GOT.
*3
Turn ON the terminating switch of the general communication module which will be a terminal.
4.2.8

Station number setting

Set each station number so that no station number overlaps.
The station number can be set without regard to the cable connection order. There is no problem even if station numbers
are not consecutive.
■1. Direct specification
Specify the station No. of the PLC to be changed when setting device.
MODE switch
RS485 station
No. switch
RS485
terminator switch
MODE
Station No.
Terminator
Station
Station
Station
No.3
No.0
No.1
GOT
Examples of station number setting
Specification range
0 to 99
Item
Station
Station
No.15
No.6
4.2 Serial connection
4
Set value
*1
1 to 3
*2
*3
4 - 29