System Configuration For Connecting To Mp3200 Or Mp3300 - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

6.3.2

System configuration for connecting to MP3200 or MP3300

MP3200,MP3300
PLC
Model name
• 100BASE-TX
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP)
MP3200
of category 5 or higher
MP3300
• 10BASE-T
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP)
of category 3 or higher
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
GT25-W, GT2505-V does not support the option device.
Connection cable
Connection cable
Maximum
*1
segment
Cable model
length
100m
GOT
GOT
*3
Model
Option device
*2
- (Built into GOT)
GT25-J71E71-100
6.3 Ethernet Connection
Communication driver
Ethernet(YASKAWA MP3000), Gateway
Number of connectable
equipment
When PLC (module):GOT is N:1
The following shows the number
of PLCs for 1 GOT
<For GT27, GT25>
TCP: 128 or less
UDP: 128 or less
<For GT21>
TCP:4 or less
UDP:4 or less
When PLC (module):GOT is 1:N
The following shows the number
of GOTs for 1 PLC (module)
TCP/UDP: 10 or less
6 - 25
6