■2. Settings by DIP switch
(1) Settings for 218TXB
Set the DIP switch (SW2) as follows.
Setting Item
N/O
Mode Selection
*1
Not used
-
10/100
Transmission Speed
F/H
Transmission Mode
INIT
Initial Startup
*2
Test
TEST
*1
Turn off all the unused switches.
When even one of those switches is on, the PLC may not normally operate.
*2
When the PLC is started with the TEST switch on, the module starts the self-diagnosis and may not perform the communication.
Turn off the switch before the communication is started.
N/O
-
10/100
F/H
-
-
INIT
TEST
OFF
ON
Set value
ON: Extended mode (13 channels, up to 1024 words)
ON
OFF: Basic mode (10 channels, up to 512 words)
OFF
ON :10Mbps
OFF
OFF :100Mbps
ON: Full duplex mode
OFF
OFF: Half duplex mode
ON: Start up by the default IP address and the engineering port
No.
OFF
OFF: Start up by the IP address and the engineering port No. set
for CP-717
ON: The module starts the self-diagnosis when the PLC is started.
OFF
OFF: The module does not start the self-diagnosis when the PLC
is started.
Setting range
-
6.3 Ethernet Connection
6
6 - 35