Mitsubishi Electric GOT2000 Series Connection Manual page 154

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(7) RS-485 connection diagram 7)
SDA
SDB
RDA
RDB
RSA
CSA
RSB
CSB
*1
*2
*3
*4
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-485 cable must be 500m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
(3) FUJI temperature controller side connector
Use the connector compatible with the FUJI temperature controller side.
For details, refer to the user's manual of the FUJI temperature controller.
■3. Connecting terminating resistors
(1) GOT side
(a)
For GT27, GT25(Except GT2505-V), GT23
Set the terminating resistor setting switch of the GOT main unit to "Enable".
(b)
For GT2505-V
Set the terminating resistor selector to "110Ω".
For the procedure to set the terminating resistor, refer to the following.
(2) FUJI temperature controller side
When connecting a FUJI temperature controller to the GOT, a terminating resistor must be connected.
5 - 12
5.3 Connection Diagram
* 3
GOT side
1
6
2
7
SG
5
3
4
8
9
Pin No. of temperature controller differs depending on the model. Refer to the following table.
Signal name
+
-
Terminating resistor should be provided for a temperature controller which will be a terminal.
Set the terminating resistor of GOT side which will be a terminal.
➠ ■3.
Connecting terminating resistors
Connect FG grounding to the appropriate part of a cable shield line.
1.4.1GOT connector specifications
1.4.3Terminating resistors of GOT
5.5 Temperature Controller Side Setting
Temperature
controller side
+ * 1
- * 1
* 4
* 4
Terminating resistor(100Ω 1/2W)
PXR3
PXR4
Pin No.
Pin No.
15
7
14
8
Temperature
controller side
+ * 1
- * 1
* 2
Model of temperature controller
PXR5/9
PXG4
Pin No.
Pin No.
1
7
2
8
PXG5/9
PXH9
Pin No.
Pin No.
1
14
2
16