(2) PC/PPI cable settings
Set the transmission speed by operating the DIP switch on the PC/PPI cable.
SWITCH1
0
0
*1
15.2.8

Precautions

■1. GOT alarm list (system alarm) function
Error information cannot be monitored when the GOT is connected to a SIEMENS PLC.
(The error information on the PLC CPU side can be monitored.)
For details on the alarm list (system alarm), refer to the following manual:
(1) When powering ON the system
Turn ON all PLC CPUs before turning ON the GOT.
If the GOT is turned ON before power-up of the PLC CPUs, restart the GOT.
(2) When powering OFF a PLC CPU at another station
When a PLC CPU at another station (the PLC CPU to which the HMI Adapter is not connected) is turned OFF,
monitoring by the GOT is stopped.
To resume the monitoring, restart the GOT.
(Monitoring will not be resumed on GOT even if the PLC CPU is turned ON again.)
15 - 12
15.2 Serial Connection
DIP switch
(down side:0, upper side:1)
1
0
1
0
1 2 3 4 5
SWITCH2
SWITCH3
0
1
Adjust with GOT settings.
GT Designer3 (GOT2000) Screen Design Manual
RS-232
PC/PPI cable
RS-485
SWITCH 123
SWITCH 4
SWITCH 5
SWITCH4
1
0
0
0
S7-200 CPU
SWITCH5
Transmission speed
*1
0
19200bps
*1
0
9600bps