8.5
Temperature Controller Side Setting
Temperature controller
RS232C/RS485 converter
8.5.1
Connecting to GREEN Series
■1. Communication settings
Make the communication settings by operating the key of the temperature controller.
(1) For the UT /UP /UM /US1000 (except UT750, UP750)
Item
Transmission speed
*1
Data bit
*1
Parity bit
*1
Stop bit
*1*2
Address
*1
Protocol selection
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
(2) For the UT750, UP750
Item
*1
Transmission speed
*1
Data bit
*1
Parity bit
*1
Stop bit
*1*2
Address
*1
Protocol selection
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
POINT
POINT
POINT
(1) YOKOGAWA temperature controller
For details of YOKOGAWA temperature controller, refer to the following manual.
➠
User's Manual of the YOKOGAWA temperature controller
(2) RS232C/RS485 converter
For details on communication settings of the RS232C/RS485 converter, refer to the following
manual.
➠
User's Manual of RS232C/RS485 converter
Model name
GREEN
UT100
UT2000
UTAdvanced
ML2-
9600bps (fixed)
7bits, 8bits
Even, odd, none
1bit, 2bits
1 to 99
0: PC link communication (without sum check)
1: PC link communication (with sum check)
RS-485 communication
High performance RS-485
communication
7bits, 8bits
Even, odd, none
1bit, 2bits
1 to 99
RS-485 communication
High performance RS-485
communication
Set value
Set value
9600bps (fixed)
9600bps, 19200bps,
38400bps
0: PC link communication
(without sum check)
1: PC link communication
(with sum check)
0: PC link communication
(without sum check)
1: PC link communication
(with sum check)
8.5 Temperature Controller Side Setting
Refer to
8.5.1
8.5.2
8.5.3
8.5.4
8.5.5
8
8 - 33