■2. Setting DIP switches
Make the settings of transmission speed, data bit configuration, communication protocol.
Setting item
Communication speed
Data bit configuration
Communication protocol
Internal data bus
termination resistor setting
Data interval extension
time
■3. Module address settings
Set the unit address using the rotary switch (address setting switch).
9 - 58
9.5 Temperature Controller Side Setting
Set value
9600bps
19200bps
38400bps
Data bit: 8bit,
Parity: None
Data bit: 8bit,
Parity: Even
Data bit: 8bit,
Parity: Odd
MODBUS
OFF
ON
0 to 99ms
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVTNT4
POINT
POINT
POINT
The rotary switch (address setting switch) is also used for the data interval extension time setting.
The setting method is the same as that of the module address.
For the data interval extension time, refer to the following.
■4.Data interval extension time settings
Dip switch
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1
2
3
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
Rotary switch
(Address setting switch)
Upper digit setting
(Set value x10)
Lower digit setting
(Set value x1)
ON
OFF
Switch position
4
5
6
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
7
8
OFF
ON