(2) DIP switch setting (SW3)
Set the communication speed and the data bit configuration using the DIP switch (SW3).
Setting item
Communication speed
Data bit configuration
(3) DIP switch settings (SW4)
Set the communication specifications and the termination resistor using the DIP switch (SW4).
Setting item
Communication specification
setting
Termination resistor setting
Dip switch(SW3)
OFF
Set value
1
4800bps
OFF
9600bps
ON
19200bps
OFF
38400bps
ON
Data bit:
8 bits,
-
Parity:
None, Stop: 2 bits
Data bit:
8 bits,
-
Parity:
None, Stop: 1 bit
Data bit:
8 bits,
-
Parity:
Even, Stop: 1 bit
Data bit:
8 bits,
-
Parity:
Odd, Stop: 1 bit
Dip switch(SW4)
ON
O N
1
2
OFF
Set value
RS-422A
RS485
Enable
Disable
ON
Switch position
2
3
4
5
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
3
4
Switch position
1
2
OFF
OFF
ON
ON
-
-
9.5 Temperature Controller Side Setting
6
7
8
-
-
-
-
-
3
4
-
-
ON
OFF
9 - 61