2.7.3 EMC Test Results

2
2
The following test results have been obtained using a system with a frequency converter, a screened control cable, a control
box with potentiometer, as well as a motor screened cable.
RFI Filter Type
H4 RFI filter
(Class A1)
0.25-11kW
3x200-240V IP20
0.37-22kW
3x380-480V IP20
H2 RFI filter
(Class A2)
1.5-45kW
3x200-240V IP20
30-90kW
3x380-480V IP20
22-90kW
3x380-480V IP54
H3 RFI filter
(Class A1/B)
1.5-45kW
3x200-240V IP20
30-90kW
3x380-480V IP20
22-90kW
3x380-480V IP54
32
VLT HVAC Basic Drive Design Guide
Conduct emission. Maximum shielded cable length
Industrial environment
EN 55011 Class A2
EN 55011 Class A1
Without
With
Without
external
external
external
filter
filter
filter
25m
25m
25m
25m
25m
50m
50m
50m
MG.18.C2.02 - VLT
Housing, trades and
light industries
EN 55011 Class B
With
Without
With
external
external
external
filter
filter
filter
50m
20m
50m
20m
20m
20m
10m
®
is a registered Danfoss trademark
Radiated emission
Industrial
Housing, trades and
environment
light industries
EN 55011 Class A1
EN 55011 Class B
Without
With
Without
external
external
external
filter
filter
filter
Yes
Yes
Yes
Yes
no
-
no
-
no
-
yes
-
yes
-
yes
-
With