I/O NUMBER ASSIGNMENT

4.6.2 I/O numbers of remote station

It is possible to allocate CPU module device input (X) and output (Y) to remote station I/O
Basic
modules and intelligent function modules and control the modules in the MELSECNET/H
Note4.4
remote network
High
Input (X) and output (Y) can be used for the refresh target (CPU module side device) of the
Performance
MELSECNET/H link I/O (LX/LY).
Note4.5
(1) CPU module I/O numbers available at remote stations
Note5
Basic
The Basic model QCPU does not support the MELSECNET/H remote I/O network.
Note4.4
Note6
High
When using the MELSECNET/H remote I/O network with the High Performance model QCPU,
Performance
check the versions of the CPU module and GX Developer.(
Note4.5
Note4.4
Note4.5
,
, the CC-Link and other remote I/O
CPU module
CC-Link module
MELSECNET/H remote I/O network
Figure 4.19 Remote station I/O numbers
When using the input (X) and output (Y) of the CPU module for the I/O numbers of
remote stations, assign the I/O numbers later than those used by the CPU module
side I/O modules and intelligent function modules.
Example: When X/Y0 to X/Y3FF (1024 points) are used by the CPU module side I/O
modules and intelligent function modules, X/Y400 and later can be used at the
remote stations.
MELSECNET/H module
Remote
Remote
station
X
0
to
Y
0 to
0 to
4.6 Concept of I/O Number Assignment
4.6.2 I/O numbers of remote station
systems.Note5Note6
station
F
:
Inupt module
F
:
Output module
:
Intelligent function module
F
Appendix 4.2)
1
2
3
4
5
6
7
8
4
- 21