9
PARAMETERS
(4) PLC RAS (PLC RAS (1)
Item
Parameter No.
WDT
setting
Initial
execution
WDT
monitoring
(watchdog
3000
time
timer)
setting
Low speed
execution
monitoring
*2
time
9
- 18
9.1 PLC Parameters
9.1.2 High Performance model QCPU, Process CPU, Redundant CPU, Universal model QCPU
Set various items for the RAS function.
Table9.15 PLC RAS list
Description
Set the watchdog timer value of
the CPU module.
Set the watchdog timer value
when an initial execution type
program is used.
H
Set the watchdog timer value
when a low speed execution
type program is used.
* 1 : When the PLC parameters of the Process CPU or Redundant CPU are set, "PLC RAS (1)" is
displayed on the PLC parameters screen of GX Developer.
* 2 : Cannot be set when the Redundant CPU and Universal model QCPU is used.
*1
)
Figure 9.15 PLC RAS
Setting range
10ms to 2000ms (10ms unit)
10ms to 2000ms (10ms unit)
10ms to 2000ms (10ms unit)
Default value
Reference
200ms
Section 3.2
No setting
Section 3.3.1
No setting
Section 3.3.3
(Continued on next page)