Transmission Delay Time; Master Station <-> Remote I/O Station; Master Station <-> Remote Device Station (Ver. 1 Compatible Slave Station) - Mitsubishi FX3U User Manual

Melsec-f, cc-link v2
Hide thumbs Also See for FX3U:
Table of Contents

Advertisement

FX
-16CCL-M User's Manual
3U
7.2

Transmission Delay Time

This section explains the transmission delay time (the time until data is transmitted).
When consistency control is being used, it becomes delay time from a consistency control completed.
7.2.1
Master station <-> Remote I/O station
1. Master station (RX) <- Remote I/O station (input)
This indicates the time from the moment a signal is input to a remote I/O station until the corresponding
master station PLC device turns ON (OFF).
Calculation expression
SM + LS × 2 + Remote I/O station processing time [ms]
- SM: Master station sequence program scan time
- LS: Link scan time
2. Master station (RY) -> Remote I/O station (output)
This indicates the time from the moment a master station PLC device turns ON (OFF) until a remote I/O
station output turns ON (OFF).
Calculation expression
SM + LS × 2 + Remote I/O station processing time [ms]
- SM: Master station sequence program scan time
- LS: Link scan time
7.2.2
Master station <-> Remote device station (Ver. 1 compatible slave station)
1. Master station (RX) <- Remote device station (RX)
This indicates the time from the moment a signal is input to a remote device station until the corresponding
master station PLC device turns ON (OFF).
Calculation expression
SM + LS × 2 + Remote device station processing time [ms]
- SM: Master station sequence program scan time
- LS: Link scan time
2. Master station (RY) -> Remote device station (RY)
This indicates the time from the moment a master station PLC device turns ON (OFF) until a remote device
station output turns ON (OFF).
Calculation expression
SM + LS × 2 + Remote device station processing time [ms]
- SM: Master station sequence program scan time
- LS: Link scan time
3. Master station (RWw) -> Remote device station (RWw)
This indicates the time from when data is set to a master station PLC device until the corresponding data on
the remote device station is changed.
Calculation expression
SM + LS × 2 + Remote device station processing time [ms]
- SM: Master station sequence program scan time
- LS: Link scan time
74
→ For details on the consistency control, refer to Subsection 6.3.6.