FUNCTIONS
(4) Setting the Output (Y) Status when Changing from STOP Status to RUN
Status
Set the output (Y) status when changing from the STOP status to the RUN status in
the PLC system of the PLC parameter dialog box.
(5) Precaution
If an output (Y) is forcibly turned ON when the CPU is in STOP status, the output (Y)
when changing from STOP status to RUN status is as shown in Table6.4.
Table6.4 Output when changing from STOP status to RUN status after forcibly turning ON output (Y) in STOP status
Output mode when changing from STOP to RUN
Output (Y) status prior to STOP is output
Output (Y) is cleared
Output mode at
STOP to RUN
Figure 6.10 PLC system screen
The status prior to STOP is output.
If output (Y) is OFF prior to STOP, ON status is not maintained.
ON status is maintained.
6.4 Setting Output (Y) Status when Changing between STOP and RUN
Output when changing from STOP status to RUN status