2 SYSTEM CONFIGURATIONS

2.3 About Use of the QD62 (E/D) with the Q12PRH/Q25PRHCPU

2.4 About Use of the QD62 (E/D) on the MELSECNET/H Remote I/O Station

2 - 4
Here, use of the QD62 (E/D) with the Q12PRH/Q25PRHCPU is explained.
(1) GX Configurator-CT
When using GX Developer to access the Q12PRH/Q25PRHCPU through the
intelligent function module on the extension base unit, GX Configurator-CT
cannot be used.
Connect a personal computer to the Q12PRH/Q25PRHCPU with a
communication path indicated below.
1
1
Direct connection to the CPU
2
Connection through an intelligent function module on the main base unit
(Through Ethernet module, MELSECNET/H module, or CC-Link module)
Here, use of the QD62 (E/D) on the MELSECNET/H remote I/O station is explained.
(1) Number of QD62 (E/D) that can be installed when the remote I/O
station is used
See Section 2.1 concerning the number of QD62 (E/D) that can be installed
when the remote I/O station is used.
(2) Limitations when using the remote I/O station
(a) The coincidence detection interrupt function cannot be used.
(b) When the QD62 (E/D) is used on the MELSECNET/H remote I/O station, a
delay will occur due to the link scan time. Therefore, fully verify that there will
be no problem with controllability in the target system.
Example) When processing is executed using the counter value input by a
sequence program, variations will occur due to a delay in the link
scan time.
2
Main base unit
Extension base unit
(GX Configurator-CT cannot be used.)