10
DEVICE EXPLANATION

10.5 Module Access Devices

10.5.1 Intelligent function module device (U \G )
(1) Definition
(2) Designation method and application example of intelligent function
10
- 59
10.5 Module Access Devices

10.5.1 Intelligent function module device (U\G)

The intelligent function module devices allow the CPU module to directly access the
buffer memories of intelligent function modules/special function modules which are
mounted on at the main base unit and extension base units.
module device
(a) Designation method
Intelligent function module devices are designated by the intelligent function
module/special function module I/O No., and the buffer memory address.
Designation method: U
\G
Figure 10.52 Intelligent function module device designation method
(b) Application example
Specify the intelligent function module device as shown in Figure 10.53 when
storing into D0 to 3 the digital output values of CH. 1 to 4 on the Q64AD analog/
digital converter module (X/Y020 to 02F) mounted at the I/O No. 020.
Figure 10.53 Intelligent function module device application example
POINT
Using the intelligent function module device allows device comments to be
attached to the buffer memory.
GX Developer Operating Manual
Buffer memory address (setting range: 0 to 65535 in decimal)
Starting I/O number of intelligent function
module/special function module
Setting
: First 2 digits of starting I/O number expressed in 3 digits
For X/Y1F0
Setting range : Q00JCPU
Q00/Q01CPU
Other CPU module : 00
BMOV
U2\G11
D0
K4
X/Y1F0
Designation: 1F
: 00
to 0F
H
H
: 00
to 3F
H
H
to FF
H
H
Q64AD
11
CH.1 Digital output value
12
CH.2 Digital output value
CH.3 Digital output value
13
CH.4 Digital output value
14

Hide quick links: