6
FUNCTIONS
(5) Procedure and setting for use of device initial values
Basic
Note6.86
Note88
Basic
Note6.86
6
- 198
6.26 Device Initial Value
In order to use the device initial values, the device initial data must be created with GX
Developer in advance, and this data must be stored as a device initial value file in the
CPU module program memory, standard RAM or memory card.
• Add the device initial value data in the project data list of GX Developer.
As the device initial value range setting screen appears, set the device initial
value range.
The number of points that can be set is up to 8000 points per range setting.
• Add the device memory data on the project data list of GX Developer.
As the device memory screen appears, set the device initial value data in the
device initial value range set above.
Figure 6.120 Device initialization range setting screen, device memory screen
POINT
When the setting on the Device initialization range setting screen is modified, be
sure to execute the "Device memory registration/diversion" operation. Refer to the
following manual for details of the operation.
GX Developer Version 8 Operating Manual
The Basic model QCPU does not support the use of a memory card.
Note6.86