Mitsubishi Q00JCPU User Manual page 877

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

APPENDICES
(17)For redundant systems (Host system CPU information
Number
Name
Meaning
Operation mode
Hot start switch
SD1512
during CPU
power out time
module start up
4 LED states
Redundant
• BACKUP
SD1585
system LED
• CONTROL
status
• SYSTEM A
• SYSTEM B
Reason(s) for
Reason(s) for
system switching
SD1588
system
that occurred in
switching
host station
*1: The information of the host CPU module is stored.
SD1510 to SD1599 are only valid for redundant systems.
They are all set to 0 for stand-alone systems.
TableApp.35 Special register
Explanation
• Shows the power out time (S) during the automatic switch from hot start
to initial start in the operation mode when the CPU module is started up.
The LED status for BACKUP, CONTROL, SYSTEM A, SYSTEM B is
stored in the following format:
b15
to
b10b9
b8
b7
b6
b5
b4
b3
b2
0
0
SYSTEM B
0: Off
1: On
2: Flicker
SYSTEM A
0: Off
1: On
2: Flicker
Stores the reason(s) for system switching on the host system.
The following values are stored corresponding to the methods for system
switching:
Initialized to 0 when the power supply is switched off and then on or the
RESET switch is set to the RESET position and then to the neutral
position.
0: Initial value (control system has not been switched)
1: Power off, Reset, H/W failure, WDT error,
2: CPU stop error (except WDT)
3: System switching request from network module
16: System switching dedicated instruction
17: System switching request from GX Developer
(When Set)
to
b0
BACKUP
0: Off
1: On (red)
5: On (orange-yellow)
2:
Flicker(red)
6: Flicker
(orange-yellow)
3: On(green)
4: Flicker(green)
CONTROL
0: Off
1: On
condition occurs)
Appendix 2 Special Register List
*1
)
Corres-
Set by
ponding
Corresponding
ACPU
CPU
D9
S (Initial)
New
Q4AR
S (status
New
change)
QnPRH
S (when
App
9
10
11
12
- 88

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents