4
I/O NUMBER ASSIGNMENT
To assign I/O numbers, follow the items below:
(1) Number of slots of base units
(2) Order of I/O number assignment
Basic
Process
Redundant
Note4.3
Note4.3
Note4.3
Note4
Basic
Basic
Process
Redundant
For the Q00JCPU, Process CPU and Redundant CPU, slim type main base units are not
available.
Note4.3
Note4.3
Note4.3
The number of slots of base units is set in Base mode.(
(a) In Auto mode
The number of slots is determined as the available number of modules mounted
to each base unit.
5 slots are assigned to a 5-slot base unit, and 12 slots are assigned to a 12-slot
base unit.
(b) In Detail mode
The number of slots set in the I/O assignment setting of the PLC parameter dialog
box is used.
The I/O numbers are assigned to the modules from left to right consecutively, starting
from 0
assigned to the module on the right of the CPU module in the main base
H
Note4.3
unit.
Note4
POINT
One Redundant CPU occupies 2 slots.
Hence, the I/O number of Slot 1 (on the right of the Redundant CPU) is X/Y0.
Main base unit (5 slots)
I/O No. on right of Redundant CPU (Slot 1) is X/Y0.
CPU
0
1
2
3
Redundant CPU
occupies 2 slots.
4.6 Concept of I/O Number Assignment
4.6.1 I/O numbers of base unit
Section 4.4)
4
Slot number
4
1
2
3
4
5
6
7
8
- 19