FUNCTIONS
(2) Explanation of specifications
Basic
Note6.14
Note15
Basic
Note6.14
6
- 60
6.11 Monitor Function
6.11.3 Forced ON/OFF for external I/O
(a) Status of the CPU module for which forced ON/OFF is available
Forced ON/OFF can be registered regardless of the status (RUN/STOP) of the
CPU module.
Note, however, that only input can be forcibly turned ON/OFF during a stop error.
Output is performed only to device Y.
(b) Registerable devices
The number of devices as many as CPU module's I/O device points can be
registered.
(
CHAPTER 2 )
(c) Target I/O for forced ON/OFF
Inputs and outputs targeted for forced ON/OFF are described below.
• I/O (X/Y) of modules on main base unit.
• I/O (X/Y) of CPU module to which LX/LY of CC-Link IE controller network
module or MELSECNET/H module is refreshed
• I/O (X/Y) of CPU module to which RX/RY of CC-Link to be refreshed
When forcibly turning ON/OFF the devices outside the above refresh ranges (ex:
empty slots), only I/O in the CPU module device memory are turned ON/OFF, and
the results are not output externally.
POINT
In a multiple CPU system, inputs and outputs of controlled modules are targeted
for forced ON/OFF.
Even when inputs and outputs of non-controlled modules are registered for forced
ON/OFF, I/O devices in other CPU modules and I/O of modules controlled by
other CPU modules are not forcibly turned ON/OFF.
(I/O devices in host CPU module turn ON/OFF.)
For details on the multiple CPU system, refer to the following manual.
QCPU User's Manual (Multiple CPU System)
The Basic model QCPU does not support the forced ON/OFF registration operation from the
Forced input output registration/cancellation screen (
The Basic model QCPU can forcibly turns ON/OFF external I/O only by executing a device test in
GX Developer.
Note6.14
Note15
(3) in this section).