Appendix 5.4.6 Forced On/Off Function Of External I/O - Mitsubishi Q00JCPU User Manual

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

APPENDICES

Appendix 5.4.6 Forced ON/OFF Function of External I/O

App
- 161
Appendix 5 Method of replacing High Performance model QCPU with Universal model QCPU
(1) Differences between High Performance model QCPU and Universal
model QCPU
(a) High Performance model QCPU
External I/O can be forcibly turned ON/OFF on the screen displayed by selecting
[Online]
[Debug]
Developer in the High Performance model QCPU.
(b) Universal model QCPU
The Universal model QCPU whose serial number (first five digits) is "10041" or
earlier does not support the forced ON/OFF function of external I/O.
External I/O can be forcibly turned ON/OFF using the replacement program
described below.
(2) Method of replacing High Performance model QCPU with Universal
model QCPU
As shown in Figure App.28, add programs, "SETX" and "SETY", on the Program
setting tab of PLC parameter.
Figure App.28 Modification on the Program setting tab of PLC parameter
The following table shows the program setting of the "SETX" and "SETY".
Program name
SETX
SETY
[Forced input output registration/cancellation] using GX
TableApp.83 Program setting of "SETX" and "SETY"
Execution type
Scan
Scan
Position where program is added
Start of Program setting (No.1)
End of Program setting