FUNCTIONS

6.25 Service Processing

6.25.1 Module service interval time read

Universal
UD
Note6.82
The module service interval indicates the time between a transient request such as
monitor, test, program write/read.
The CPU module can monitor the service interval time (time from service acceptance to
next service acceptance) of the intelligent function module, network module or GX
Developer.
This indicates the frequency at which access to the CPU occurs from outside.
(1) Reading
Note84
Universal
The Universal model QCPU cannot read module interval time.
UD
Note6.82
methodNote84
To read the module service interval time, operate the following special relay and
special registers shown in Table6.57 and Table6.58.
Number
Name
Module service interval time
SM551
read
Number
Name
Module service interval time
SD550
measured module
SD551,
Module service interval time
SD552
Table6.57 Special relay
Description
Turning this relay from OFF to ON reads to SD551
and SD552 the module service interval time of the
intelligent function module specified in the special
register SD550.
ON: Read
OFF: No processing
Table6.58 Special registers
Description
Set the I/O number of the module whose module
service interval time will be measured.
Set the I/O number of the peripheral device
connected to the RS-232 or USB interface of the
CPU module to FFFF
Stores the service interval time from the module
specified in SD550 when SM551 is turned on.
SD551: 1ms units (range 0 to 65535)
SD552: 100 s units (range 0 to 900, stored
at intervals of 100 s)
(Example) When module service interval time is
123.4ms
SD551 = 123, SD552 = 400