APPENDICES
(3) System clocks/counters
Number
Name
ON
SM400
Always ON
OFF
ON
SM401
Always OFF
OFF
After RUN, ON for 1
ON
SM402
scan only
OFF
After RUN, OFF for 1
ON
SM403
scan only
OFF
Low speed execution
ON
SM404
type programON for 1
OFF
scan only after RUN
Low speed execution
type programAfter
ON
SM405
RUN, OFF for 1 scan
OFF
only
0.005s
SM409
0.01 second clock
0.05s
SM410
0.1 second clock
0.1s
SM411
0.2 second clock
0.5s
SM412
1 second clock
1s
SM413
2 second clock
ns
SM414
2n second clock
TableApp.4 Special relay
Meaning
• Normally is ON
• Normally is OFF
• After RUN, ON for 1 scan only.
• This connection can be used for scan execution type
programs only.
• When an initial execution type program is used, this
relay turns OFF at the END processing of the scan
execution type program in the first scan after RUN.
1 scan
ON
Initial
OFF
execution
type program
• After RUN, ON for 1 scan only.
• After RUN, OFF for 1 scan only.
• This connection can be used for scan execution type
programs only.
• When an initial execution type program is used, this
relay turns OFF at the END processing of the scan
execution type program in the first scan after RUN.
ON
1 scan
OFF
Initial
execution
type program
• After RUN, OFF for 1 scan only.
• After RUN, ON for 1 scan only.
1 scan
• This connection can be used for low speed execution type
programs only.
• After RUN, OFF for 1 scan only.
• This connection can be used for low speed execution type
1 scan
programs only.
• Repeatedly changes between ON and OFF at 5-ms
interval.
• When Programmable Controller power supply is
turned ON or a CPU module reset is performed,
0.005s
goes from OFF to start.
(Note that the ON-OFF status changes when the
designated time has elapsed during the execution of
the program.)
0.05s
• Repeatedly changes between ON and OFF at each
designated time interval.
• When Programmable Controller power supply is
0.1s
turned ON or a CPU module reset is performed,
goes from OFF to start.
(Note that the ON-OFF status changes when the
0.5s
designated time has elapsed during the execution of
the program.)
1s
• This relay alternates between ON and OFF at
intervals of the time (unit: s) specified in SD414.
• When Programmable Controller power supply is
turned ON or a CPU module reset is performed,
ns
goes from OFF to start.
(Note that the ON-OFF status changes when the
designated time has elapsed during the execution of
the program.)
Explanation
(When Set)
S (Every END
processing)
S (Every END
processing)
S (Every END
processing)
1 scan of scan
execution type
program
S (Every END
processing)
S (Every END
processing)
1 scan of scan
execution type
program
S (Every END
processing)
S (Every END
processing)
S (Every END
processing)
S (Status change)
S (Status change)
S (Status change)
Appendix 1 Special Relay List
Corres-
ponding
Set by
Corresponding
ACPU
CPU
M9
M9036
M9037
QnA
Qn(H)
M9038
QnPH
QnPRH
QnU
New
Q00J/Q00/Q01
QnA
Qn(H)
M9039
QnPH
QnPRH
QnU
New
Q00J/Q00/Q01
New
QnA
Qn(H)
QnPH
New
Qn(H)
QnPH
New
QnPRH
QnU
M9030
M9031
M9032
M9033
M9034form
at change
App
9
10
11
12
- 8