Remote Pause - Mitsubishi Q00JCPU User Manual

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS

6.6.2 Remote PAUSE

(1) Definition of Remote PAUSE
The remote PAUSE performs PAUSE of the CPU module externally with the CPU
module RUN/STOP switch (RUN/STOP/RESET switch for the Basic model QCPU
and Universal model QCPU) at RUN position.
In the PAUSE status, the CPU module operation is stopped with the ON/OFF states of
all outputs (Y) held.
(2) Applications of remote PAUSE
This can be used to maintain the output (Y) on even if the CPU module is changed to
STOP status, in such areas as process control.
(3) Remote PAUSE method
Remote PAUSE operation can be performed either by the PAUSE contact or by GX
Developer or external device using MC protocol.
(a) Method with PAUSE Contact
The PUASE contact is set at the "PLC system" tab screen in the "(PLC)
Parameter" dialog box of GX Developer.
The device ranges that can be set are shown in Table6.12.
Table6.12 Device ranges that can be set to PAUSE contact
CPU module
Basic model QCPU
High Performance model QCPU
Process CPU
Redundant CPU
Universal model QCPU
• The PAUSE status contact (SM204) is turned on when the END processing is
executed for the scan with both PAUSE contact and PAUSE permission flag
(SM206) on.
• When the PAUSE contact is off or SM206 is turned off, the PAUSE status is
canceled, and the sequence program calculation is performed again from
step 0.
0
ON
OFF
Remote PAUSE
contact
OFF
SM206
OFF
SM204
RUN/PAUSE
status
Figure 6.17 PAUSE Time Chart with PAUSE Contact
Available device range
Input X0 to 7FF
Input X0 to 1FFF
END
0
END
ON
ON
ON when
PAUSE
condition met
RUN
PAUSE
PAUSE status
6.6 Remote Operation
6.6.2 Remote PAUSE