Mitsubishi Q00JCPU User Manual page 590

Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

9
PARAMETERS
Item
Parameter No.
Points occupied by empty
1007
slot *4
Interrupt counter
start No.
1008
Fixed scan interval
(n : 28 to 31)
X Input
100F
Y Output
1010
Buffer read
1011
Buffer write
1012
Service processing
1013
setting*3
Latch data backup
operation enabled
1014
*3
contact
Interrupt program/fixed
1008
scan program setting
Module synchronization
100C
*1
100D
A-PLC
9
- 16
9.1 PLC Parameters
9.1.2 High Performance model QCPU, Process CPU, Redundant CPU, Universal model QCPU
Table9.13 PLC system list (Continued)
Description
Set the number of empty slots on
the main base unit/extension
H
base unit.
Set the start No. of the interrupt
*4
counters.
H
Set the execution intervals of the
interrupt pointers (I28 to 31).
H
St the fixed scan interval, high-
H
speed I/O refresh setting and
H
high-speed buffer transfer
setting of the high-speed
H
interrupt pointer I49.
Select the service processing
execution method from the
followings.
• Execute the process as the
scan time proceeds
H
• Specify service process time
• Specify service process
execution counts
• Execute it while waiting for
constant scan setting
Sets the enabled contact device
No. at the time of backup of latch
H
data to the standard ROM.
Set whether an interrupt
program is executed at high
H
speed or not.
Set whether a CPU module
startup is synchronized with an
H
intelligent function module
startup.
Set whether the special relays/
special registers for MELSEC-A
series (SM1000/SD1000 to
H
SM1299/SD1299) will be used or
not.
* 1 : Cannot be set when the Redundant CPU and Universal model QCPU is used.
* 2 : High-speed interrupt setting can be made only when the High Performance model QCPU is used.
* 3 : Can be set only when the Universal model QCPU is used.
* 4 : The Universal model QCPU cannot set the head number of the interrupt counter.
Setting range
0 points/16 points/32 points/64
points/128 points/256 points/512
points/1024 points
(Can be set up to the number of
counter setting points - 256)
0.5ms to 1000ms
(0.5ms unit)
I49 : 0.2ms to 1.0ms
(0.1ms unit)
• 1 to 99 % (1 percent units)
• 1 to 10 times (1 time units)
• 0.2ms to 1000ms (0.1ms
units)
• With/without setting
----
Execute at high speed/Do not
execute at high speed
Synchronize/Do not synchronize
with intelligent function module
startup
Use/Do not use the special
relays/special registers SM1000/
SD1000 and later
Default value
Reference
16 points
Section 4.6.1(5)
No setting
Section 10.2.11(4)
I28:100.0ms
I29:40.0ms
Section 10.11
I30:20.0ms
I31:10.0ms
Section 3.1.3
No setting
Section 6.22
Execute the
process as the scan
Section 6.25.2
time proceeds: 10%
Not used
Section 6.29
Do not execute at
Section 3.1.3
high speed
Synchronize with
intelligent function
----
module startup
Use the special
relays/special
Section 10.3.2
registers SM1000/
Section 10.3.3
SD1000 and later