6.2

Message: SINEMA configuration not yet accepted

When the following message is displayed in the display area an error has occurred
transferring the configuration from STEP 7 Basic / Professional as of V13 to the device:
"SINEMA Configuration not accepted yet. With restart of device, all configuration changes
will be lost."
One possible cause is, for example, that during transfer the device was not reachable.
If you now change a parameter directly on the device (WBM/CLI/SNMP) these changes are
lost when the device restarts.
Solution
1. Open the relevant STEP 7 project in STEP 7 Basic / Professional
2. Open the project view.
3. Select the device in the project tree.
4. Select the "Go to network view" command in the shortcut menu.
5. Select the device in the network view.
6. In the shortcut menu of the selected device select the command "SCALANCE
configuration > Save as start configuration".
Result
The configuration is saved on the device. The message is no longer visible in the display
area. A configuration change directly on the device is no longer lost due to a restart of the
device.