Siemens SCALANCE XB-200 Configuration Manual page 154

Industrial ethernet switches
Hide thumbs Also See for SCALANCE XB-200:
Table of Contents

Advertisement

Configuring with Web Based Management
5.4 The "System" menu
Description of the displayed boxes
The page contains the following boxes:
● PROFINET Device Diagnostics
Shows whether PROFINET is enabled ("On") or disabled ("Off").
● PROFINET Device Diagnostics for next boot
Set whether PROFINET will be enabled ("On") or disabled ("Off") after the next device
restart.
Note
PROFINET and EtherNet/IP
When PROFINET is turned on, EtherNet/IP is turned off. The switchover from PROFINET
and EtherNet/IP has no effect on DCP.
Note
PROFINET AR Status
If a PROFINET connection is established; in other words the PROFINET AR status is
"Online", you cannot disable PROFINET.
● PROFINET AR Status
This box shows the status of the PROFINET connection; in other words whether the
device is connected to a PROFINET controller "Online " or "Offline".
Here, online means that a connection to a PROFINET controller exists, that this has
downloaded its configuration data to the device and that the device can send status data
to the PROFINET controller. In this status known as "in data exchange", the parameters
set via the PROFINET controller cannot be configured.
● PROFINET Name of Station
This box displays the PROFINET device name according to the configuration in HW
Config of STEP 7.
● Restart with PROFINET Defaults
Click this button to restore the default settings of the PROFINET profile and to restart the
device. You must confirm the restart in a dialog box. The dialog box displays the settings
specially made for operation with the PROFINET protocol.
154
NOTICE
By resetting all the settings to the default settings of a profile, the IP address is also lost.
Following this, the device can only be accessed via the serial interface, using the
Primary Setup Tool or using DHCP.
With the appropriate attachment, a previously correctly configured device can cause
circulating frames after the reset and therefore the failure of the data traffic.