Siemens SCALANCE XB-200 Configuration Manual page 30

Industrial ethernet switches
Hide thumbs Also See for SCALANCE XB-200:
Table of Contents

Advertisement

Technical basics
4.4 Redundancy mechanism
Ring port 1 / ring port 2
Here, select the port you want to configure as ring port 1 and ring port 2.
With devices with more than 8 ports, not all ports can be selected as ring port.
The drop-down list shows the selection of possible ports for each device type. If the ports are
specified in the factory, the boxes are grayed out.
NOTICE
Ring ports after resetting to factory settings
If you reset to the factory settings, the ring port settings are also reset.
If other ports were used previously as ring ports before resetting, with the appropriate
attachment, a previously correctly configured device can cause circulating frames and
therefore the failure of the data traffic.
Diagnostic interrupts
Enable the "Diagnostic interrupts" option, if you want diagnostic interrupts relating to the
MRP status on the local CPU to be output.
The following diagnostic interrupts can be generated:
● Wiring or port error
Diagnostic interrupts are generated if the following errors occur at the ring ports:
– Connection abort on a ring port
– A neighbor of the ring port does not support MRP.
– A ring port is connected to a non-ring port.
– A ring port is connected to the ring port of another MRP domain.
● Status change active/passive (redundancy manager only)
If the status changes (active/passive) in a ring, a diagnostics interrupt is generated.
Parameter assignment of the redundancy is not set by STEP 7 (redundancy alternatives)
This option only affects SCALANCE X switches. Select this option if you want to set the
properties for media redundancy using alternative mechanisms such as WBM, CLI or SNMP.
If you enable this option, existing redundancy settings from WBM, CLI or SNMP, are retained
and are not overwritten. The parameters in the "MRP configuration" box are then reset and
grayed out. The entries then have no meaning.