Siemens SCALANCE XB-200 Configuration Manual page 193

Industrial ethernet switches
Hide thumbs Also See for SCALANCE XB-200:
Table of Contents

Advertisement

– MRP Auto-Manager
– MRP Client
– HRP Client
– HRP Manager
● Ring ports
Here, you set the ports to be used as ring ports in ring redundancy.
The ring port you select in the left-hand drop-down list is the "Isolated Port" in HRP.
The factory setting defines the following ring ports:
SCALANCE XB-200/XC-200/XP-200 Web Based Management
Configuration Manual, 07/2016, C79000-G8976-C360-04
In the "MRP Auto Manager" mode, the devices negotiate among themselves to
establish which device will adopt the role of "MRP Manager". The device with the
lowest MAC address will always become "MRP Manager". The other devices
automatically set themselves to "MRP Client" mode.
In contrast to the setting "Automatic Redundancy Detection", the devices are not
capable of detecting whether or not an HRP manager is in the ring.
Note
MRP configuration in STEP 7
If you set the role "Manager (Auto)" or "Manager" for the device in STEP 7, in both
cases, "MRP Auto Manager" is displayed on this WBM page. In the display in the CLI,
a distinction is made between the two roles.
The device adopts the role of MRP client.
The device adopts the role of HRP client.
Te device adopts the role of HRP manager.
When you configure an HRP ring, one device must be set as HRP manager. For all
other devices, "HRP Client" or "Automatic Redundancy Detection" must be set.
Devices
SCALANCE XB208 and XB216
SCALANCE XB205-3
SCALANCE XB213-3
SCALANCE XC206-2SFP, XC208, XC216 and
XC224
SCALANCE XC206-2
SCALANCE XP208
SCALANCE XP216
Configuring with Web Based Management
5.5 The "Layer 2" menu
Factory setting ring ports
P0.1 and P0.2
P0.7 and P0.8
P0.15 and P0.16
P0.1 and P0.2
P0.7 and P0.8
P0.1 and P0.2
P0.10 and P0.12
193