YASKAWA CIMR-JC4A0002BAA Quick Start Manual page 107

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

4.5 Basic Operation
No.
Parameter Name
Terminal AM Monitor
H4-01
Selection
H4-02
Terminal AM Output Gain
<1>
H4-03
Terminal AM Bias Setting
<1>
<1>
The parameter can be changed during run.
n
Changing Analog Output Settings
The following example illustrates how to program analog output terminal AM to generate a
signal proportional to drive output current (monitor U1-03).
Using H4-01 to Display Monitor Contents
1.
Turn on the power to the drive. The initial display appears.
2.
Press
until the Parameter setting menu is displayed.
3.
Press
to enter the Parameter setting menu.
4.
Press
and
5.
Press
to display the value currently set to H4-01.
6.
Press
and
7.
Save the setting by pressing
8.
The display automatically returns to the parameter setting menu.
9.
Press the
key until back at the Top Screen.
Adjusting the Analog Output Terminal Voltage with H4-02 and H4-03
Note:
This example continues from Step 3 in the previous example.
106
Select the data to output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in Uo-oo. For
example, enter "103" for U1-03.
When using this terminal as a through terminal or when not using it at all, set
"000" or "031".
Sets the voltage level gain of terminal AM. The bias to be added ranges from
0 to +/- 10% when 10 V is assumed to be 100%.
Sets the voltage level bias for terminal AM.
The bias added is 0 to ±10% with a maximum voltage output of 10 V as 100%.
Step
to select H4-01.
to set the output current (103).
.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide