4.5 Basic Operation
n
V/f Pattern Setting Examples
This section provides examples of how to set a V/f pattern using E1-04 to E1-10.
Example
Specification
A
B
60 Hz (default setting)
C
60 Hz (with 50 Hz base)
D
72 Hz (with 60 Hz base)
E
50 Hz, Heavy Duty 2
F
50 Hz, Heavy Duty 1
G
50 Hz, Heavy Duty 1
H
50 Hz, Heavy Duty 2
I
50 Hz, mid starting torque
J
50 Hz, high starting torque
K
60 Hz, mid starting torque
L
60 Hz, high starting torque
M
90 Hz (with 60 Hz base)
N
120 Hz (with 60 Hz base)
O
180 Hz (with 60 Hz base)
The following tables show details on V/f patterns.
The following graphs are for 200 V class drives. Double the values when using a 400 V class
drive.
V/f Pattern Examples
Table 4.8 Constant Torque Characteristics, Examples A to D
Example A
50 Hz
200
16
12
0
1.3 2.5
50
Frequency (Hz)
102
Table 4.7 V/f Pattern Examples
Characteristic
50 Hz
High starting torque
60 Hz
Example B
(default)
200
16
12
0
1.5 3
Frequency (Hz)
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
For general purpose applications. Torque
Constant torque
remains constant regardless of changes to
speed.
For fans, pumps, and other applications
Derated torque
that require torque derating relative to the
load.
Select high starting torque when:
• Wiring between the drive an motor
• A large amount of starting torque is
• An AC reactor is installed
When operating at greater than 60 Hz the
Constant output
output voltage will be constant.
Example C
60 Hz
200
16
12
60
0
1.5 3
Frequency (Hz)
Application
exceeds 150 m
required
Example D
200
16
12
50
60
0
1.5 3
Frequency (Hz)
72 Hz
60
72