B.2 Parameter Table
No.
Name
Selects the detection of input current phase loss,
power supply voltage imbalance, or main circuit
Input Phase
electrolytic capacitor deterioration.
Loss
L8-05
0: Disabled
Protection
1: Enabled
Selection
Note: This parameter is disabled in 200 V single-
phase drives.
Controls the heatsink cooling fan operation.
Heatsink
0: Fan On-Run Mode - Fan will operate only when
Cooling Fan
L8-10
the drive is running and for 60 seconds after stop.
Operation
1: Fan always on - Cooling fan operates whenever the
Selection
drive is powered up.
Ambient
Used to input the ambient temperature. This value
L8-12
Temperature
adjusts the drive oL2 detection level.
Setting
Selects the software current limit function. Typically
Soft CLA
no adjustment is required.
L8-18
Selection
0: Disabled
1: Enabled
Selects the installation type:
Installation
0: IP20/IP00 Drive
L8-35
Method
1: Side-by-Side Mounting
<3>
Selection
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
Provides protection to the IGBTs by reducing the
carrier frequency at low speeds.
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the whole speed range
Carrier
L8-38
Frequency
Reduction
<1>
When enabled, the drive stops accelerating when it exceeds the value of L3-02, Stall Prevention Level. The drive
decelerates after 100 ms and begins accelerating again after restoring the current level.
<2>
Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).
<3>
This parameter is not reset to the default value when the drive is reinitialized using A1-03.
228
Description
Current
ND
HD
200 V Single Phase
80% of HD
400 V: 60% of HD
0
2
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
C6-02
Carrier Frequency
10 (8)
15
Range Def. Mode
0, 1
1
O
0, 1
0
O
-10 to
30 °C
O
50
0, 1
1
O
0 to 3
0
O
0 to 2
1
O
Addr.
Pg.
Hex
4B1
–
4B6
–
4B8
–
4BE
–
4EC
–
4EF
–